33kv outdoor electric meter

33kv outdoor electric meter
Product Detailed
Related Categories:Energy Meters
1. Stretch forming tank, no leak 2. Amorphous metals core 3. Japanese silicon steel core 4. electrostatic spray steel for box

33kV high voltage CT PT combined units for metering

Description

The combined transformer (another name is metering tank) is one kind of outdoor power measuring device, which is composed of two sets single-phase wholly insulated voltage transformers, forming three-phase V/V wiring, and two current transformers are separately series connected to A and C phase.

The JLS-35,metering tank is one upgraded product based on old product of same kind, just adding moisture-proof device onto oil tank's cover, which could effectively prevent external humidity from entering into oil, so as to prolong service life of product, while, compared with old product, its advantage contains larger capacity, smaller volume and weight, simplifying installing.

This product is applied to certain outdoor circuit of AC50-60Hz, rated volt being 35kV or lower, to be used for metering of current, voltage and electric energy etc. this product is suitable for rural outdoor transformer substation, miniature transformer station and substation of industrial enterprise etc. Adding active and reactive energy meter onto combined transformer is named as high volt power metering tank.

35kV high voltage electric meter box (power distribution) measuring box

Technical data

Metering  tank conforms to given provisions in GB17201-2006 <combined transformer>;Current   transformer conforms to given provisions in GB1208-2006 and IEC 660044-1;Voltage   transformer conforms to given provisions in GB1207-2006 and IEC 60044-2 ;The   zinc oxide arrester must be installed at certain position with less-than-one meter distance away from product's installation place, for lightning protection.
JLS-10 Voltage transformer technical data
TypeRated primary voltage(kV)Rated secondary voltage(V)Maximum voltage(kV)Accurate level and output capacity COSφ=0.8(lag)(VA) Maximum output capacity (VA)
0.20.5
JLS-103510038.52050640

 

JLS-10 Current transformer technical data
Rated primary current (A)Rated secondary current(A)Accurate level and output capacity COSφ=0.8(lag)(VA)1S Shorttime thermal currentRated peak withstand current
0.2S
15-100510600I1n150I1n

 

 

 

 

 