- Contact Person : Mr. Huang Nico
- Company Name : Zhejiang Shanghu Electrical Co., Ltd.
- Tel : 86-577-62782777
- Fax : 86-577-62755565
- Address : Zhejiang,yueqing,Xiangshan Industrial Park, Yueqing city, Zhejiang province, China
- Country/Region : China
- Zip : 325604
35 kV high - voltage power metering
35 kV high voltage transformer for metering
JLSZV-35 JLSZV-35 Description
The combined transformer (another name is metering tank) is one kind of outdoor power measuring device, which is composed of two sets single-phase wholly insulated voltage transformers, forming three-phase V/V wiring, and two current transformers are separately series connected to A and C phase.
The JLS-35,metering tank is one upgraded product based on old product of same kind, just adding moisture-proof device onto oil tank's cover, which could effectively prevent external humidity from entering into oil, so as to prolong service life of product, while, compared with old product, its advantage contains larger capacity, smaller volume and weight, simplifying installing.
This product is applied to certain outdoor circuit of AC50-60Hz, rated volt being 35kV or lower, to be used for metering of current, voltage and electric energy etc. this product is suitable for rural outdoor transformer substation, miniature transformer station and substation of industrial enterprise etc. Adding active and reactive energy meter onto combined transformer is named as high volt power metering tank.
35 KV Combined CT PT unit Ct-Pt Metering Units Instrument Transformer (Ct & Pt)
Technical data
Metering tank conforms to given provisions in GB17201-2006 <combined transformer>;Current transformer conforms to given provisions in GB1208-2006 and IEC 660044-1;Voltage transformer conforms to given provisions in GB1207-2006 and IEC 60044-2 ;The zinc oxide arrester must be installed at certain position with less-than-one meter distance away from product's installation place, for lightning protection.Current transformer data | ||||||
Rated primary current(A) | Rated secondary current(A) | Accuracy class and output (VA) | 1s rated short-time thermal current(kA) | Rated dynamic stable current (kA) | ||
0. 2S | 0.2 | 0. 5S | ||||
5, 10, 15, 20, 25, 30, 40, 50, 75, 100, 150, 200, 300 | 5 | 10 | 10 | 10 | 751ln | 187. 51ln |
Voltage transformer data | ||||||
Type | Rated primary voltage(kV) | Maximum system voltage(kV) | Rate secondary voltage(V) | Accuracy class and output (VA) | limit output (VA) | |
0.2 | 0. 5 | |||||
JLSZV-35 | 35 | 40.5 | 100 | 30 | 50 | 1000 |
35 kV high - voltage power metering